Microprocessor and Stored-Energy Switch Operators
For Automatic Source Transfer Padmounted and Metal-Enclosed Switchgear
15 kV 27 kV |
|
 |
|
 |
|
|
|
 |
|
|
| Click here to view product detail pages. |
|
|
Stored-Energy Switch Operator includes switch-position indicator, decoupling lever, decoupling indicator, operation counter, shaft to manually charge switch if control power is lost, ports for emergency manual tripping and pushbuttons for local operation. Decoupling lever isolates switch from the switch operator so that functional testing can be performed without opening and closing the switches . . . the load circuit remains energized. |
|
|
|
 |
|
|
| Addressable Automatic Transfer Microprocessor Control at left has keypad entry and LCD display; event log to record operations; field-selectable settings for timers and operating parameters; and software intelligence to initiate control operations based on programmed settings. |
|
|
Features
Source-voltage indicating lamps
Auto/manual selector
Automatic/hold return
Preferred/alternate source selection
Test buttons to simulate loss of source voltage, with pushbutton to return
Optional overcurrent lockout with test pushbutton provides blocking for faults internal to switchgear
|
|
|
|
|
|
|
SCADA-Controlled Switch Operators
For Remote Supervisory Control Switchgear
15 kV 27 kV |
|
|
 |
|
 |
|
|
|
|
Auto-jet® Loadbreak Switches
5 to 38 kV |
|
 |
|
|
Features
UL® recognized at 5 and 15 kV
600 amp at loadbreak to 38 kV
1200 amp interrupting, 5 and 15 kV
Single- and 3-phase
Front chain drive
Side-operated direct drive
Up to 61 kA asym momentary
3-time fault close at 40 kA amps asym to 38 kV |
|
|
|
Vacuum Circuit Breaker
15 kV 95 BIL |
|
 |
|
|
Features
600 or 1200 amp continuous
12000 or 18000 amps interrupting
Optional visible disconnect
Optional grounding of visible disconnect
Manual, shunt-trip or undervoltage release
Optional electrical closing and auxiliary switches
Meets Mine Safety Health Administration (MSHA) standards |
|
|
|
|
Fuse Mountings
5 to 35 kV |
|
 |
|
 |
|
|
Features
200 amp loadbreak
3-time fault close
Maximum 720 amp non-loadbreak
Cycloaliphatic epoxy insulators
Accommodates all types of expulsion and current-limiting fuses |
|
|
|
Loadbreak Fuses |
|
|
|
Non-Loadbreak Fuses |
|
|
|
|
|
|
Insulators and Bushings
5 to 38 kV |
|
 |
|
|
Features
Cycloaliphatic epoxy
100% X-rayed
Insulators tested to ANSI C29.1
Bushings meet ANSI 386
Self-scouring homogeneous material
Generous leakage distance |
|
|
 |
|
|
|
 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|